PVC Insulated, Single Core Cable, 450/750V

Application

These cables are used for switchboard and control panel wiring, and for fixed wiring within other enclosures or apparatus where the cable is not accessible without the use of tools.

Standard

  • AS/NZS 5000.2
  • AS 3008
  • AS 1125

Cable Construction

CONDUCTOR Plain annealed copper.
Maximum operating temperature: 90°C
INSULATION PVC V90
INSULATION COLOUR: Red/Black
SHEATH: Polyvinylchloride compound PVC 3V90
SHEATH COLOUR: Orange, other colors are available upon requestWhite, other colors are available upon request

Technical Characteristics

PVC Insulated, Single Core Cable

CONDUCTOR
NOMINAL AREA MM2
CURRENT RATINGS ELECTRICAL CHARACTERISTICS
UNENCLOSED IN AIR
A
SURROUNDED
BY THERMAL
INSULATION A
BURIED IN DUCTS
A
MAXIMUM
DC
RESISTANCE
@20°C
OHM/KM
MAXIMUM AC
RESISTANCE
@75°C
OHM/KM
REACTANCE OHM/KM SINGLE PHASE
VOLTAGE DROP
MV/AM
1 15 26 20 18.1 27.0 0.168 54.0
1.5 18 34 26 13.6 17.3 0.157 34.6
2.5 26 47 36 7.41 9.45 0.143 18.9
4 35 62 46 4.61 5.88 0.137 11.8
6 46 78 58 3.08 3.93 0.128 7.86
10 62 103 78 1.83 2.33 0.118 4.68
16 82 132 100 1.15 1.47 0.111 2.94

Cable Parameter

NOM. CONDUCTOR
AREA MM2
CONDUCTOR NO./ OD NOM. INSULATION
THICKNESS MM
NOM. SHEATH
THICKNESS MM
NOM. OVERALL
DIAMETER MM
APPROX. MASS KG/KM
1.0 1/1.13 0.6 0.9 4.1 30
1.5 7/0.50 0.6 0.9 4.4 35
2.5 7/0.67 0.7 1 5.1 55
4 7/0.85 0.8 1.1 6.0 80
6 7/1.04 1.0 1.1 6.6 100
10 7/1.35 1.0 1.2 7.8 145
16 7/1.70 1.0 1.3 9.1 225